Previous Scalar 
Next Scalar 
-- upsBasicControl MIB group ( 1.3.6.1.4.1.318.1.1.1.6.1 )
-- iso(1). org(3). dod(6). internet(1). private(4). enterprises(1). apc(318). products(1). hardware(1). ups(1). upsControl(6). upsBasicControl(1)
upsBasicControlConserveBattery OBJECT-TYPE 
-- 1.3.6.1.4.1.318.1.1.1.6.1.1.0
-- iso(1). org(3). dod(6). internet(1). private(4). enterprises(1). apc(318). products(1). hardware(1). ups(1). upsControl(6). upsBasicControl(1). upsBasicControlConserveBattery(1). 0
 SYNTAX INTEGER  {  
 
 noTurnOffUps  (1), 
 turnOffUpsToConserveBattery  (2) 
  }
 ACCESS read-write  
 DESCRIPTION     
 "Setting this variable to turnUpsOffToConserveBattery(2)
causes a UPS on battery to be put into 'sleep' mode. The
UPS will turn back on when utility power is restored.
Attempting to turn off a UPS that is not on battery will
result in a badValue error.

Setting this value to noTurnOffUps(1) has no
effect.

The value noTurnOffUps(1) will always be returned
when the variable is read."
::= { upsBasicControl 1  }